PI DATE: December 2004
OUTPUT Power CAPACITY: 8,000 VA ; OUTPUT Power CAPACITY: 5,600 Watts
MAX CONFIGURABLE POWER: 8,000 VA ; MAX CONFIGURABLE POWER: 5,600 Watts
NOMINAL OUTPUT VOLTAGE: 230V; OTHER I/P VOLTAGES: 220V, 240V, 380V, 415V
OUTPUT VOLTAGE: Configurable for 220 : 230 or 240 nominal output voltage
OUTPUT VOLTAGE DISTORTION: Less than 5% at full load
OUTPUT FREQUENCY (sync to mains): 47-63Hz
CREST FACTOR: Upto 5 : 1; WAVEFORM TYPE: Sinewave
OUTPUT CONNECTIONS: (1) Hard Wire 3-wire (H N + G)
(8) IEC 320 C13 ; (6) IEC 320 C19
BYPASS: Internal Bypass (Automatic and Manual)
NOMINAL I/P VOLTAGE: 230V, 400V 3PH; I/P FREQ: 45 - 65 Hz (auto sensing)
INPUT CONNECTION TYPE: Hard Wire 3 wire (1PH+N+G)
INPUT VOLTAGE RANGE FOR MAIN OPERATIONS: 155 - 276, 290 - 480 (3:1) V
BATT: Maint-free sealed Lead-Acid batt w/suspended electrolyte: leakproof
PRE-INSTALLED BATTERIES: 2; RBC QUANTITY: 2; REPLACEMENT CARTRIDGE: SYBT5
TYPICAL BACKUP TIME AT HALF LOAD: 20.2 minutes (2800 Watts)
TYPICAL BACKUP TIME AT Full LOAD: 7.5 minutes (5600 Watts)
EXTENDED RUN OPTIONS: APC Symmetra LX 8kVA Scalable to 8kVA N+1
Rack-mount, 220/230/240V or 380/400/415V
INTERFACE PORT: DB-9 RS-232, Smart-Slot
AVAILABLE SMART SLOT INTERFACE QUANTITY: 1; RUNTIME CHART: Symmetra LX
PRE-INSTALLED SMARTSLOT CARDS: AP9619 * Emergency Power Off (EPO)
DIMENSIONS: (H x W x D)(cm): 57 x 47 x 69; NET WEIGHT: 178kg
Rack HEIGHT: 13U; COLOUR: Black, Silver; UNITS per PALLET: 1