To find the right Consumables for your Printer use the search below with your Printer Model or Cartridge Part # .
PI DATE: December 2004
O/P Power CAPACITY: 16,000 VA; 11,200 Watts
MAX CONFIGURABLE POWER: 16,000 VA; 11,200 Watts
NOMINAL Output VOLTAGE: 230V
Output VOLTAGE: Note Config for 220 : 230 or 240 nominal output voltage
Output VOLTAGE: Distortion less than 5% at full load
Output FREQUENCY: (sync to mains) 47-63Hz
CREST FACTOR: Upto 5:1; WAVEFORM TYPE: Sinewave
Output Connections (1) Hard Wire 3-wire (H N + G)
BYPASS: Internal Bypass (Automatic and Manual)
NOMINAL I/P VOLT: 230V, 400V 3PH; I/P FREQUENCY: 45 - 65 Hz (auto sensing
I/P CONN TYPE: Hard Wire 3 wire (1PH+N+G); Hard Wire 5-wire (3PH + N + G)
INPUT VOLTAGE RANGE FOR MAIN OPERATIONS 155 - 276, 290 - 480 (3:1) V
OTHER INPUT VOLTAGES 220V, 240V, 380V, 415V
BATT: Maintenance-free sealed Lead-Acid - suspended electrolyte:leakproof
PRE-INSTALLED BATT: 4; REPLACEMENT Battery CART: SYBT5; RBC QUANTITY: 4
TYPICAL Backup TIME AT HALF LOAD: 20.3 minutes (5600 Watts)
TYPICAL Backup TIME AT Full LOAD: 7.5 minutes (11200 Watts)
Extended RUN OPTIONS: APC Symmetra LX 16kVA Scalable to 16kVA N+1
Tower, 220/230/240V or 380/400/415V
Interface PORT: DB-9 RS-232, Smart-Slot
AVAILABLE Smart Slot Interface QTY: 1; PRE-INSTALLED SMARTSLOT CARD: AP9619
* Emergency Power Off (EPO)
DIMENSIONS (Max H x W x D)(cm): 94 x48 x 73; NET WEIGHT: 308kg
COLOUR: Black, Silver; UNITS per PALLET: 1